Museum Entrance Museum Entrance Museum
Museum
Friends of Durham Mining Museum
Events Calendar
e-Books and Books for sale
Photograph Gallery
Document Archive
Main Document Archive
Newspaper Articles
Local Record Extracts
D.M.A. Document Archive
Transactions of I.M.E.
Miners' Welfare
N.C.B. Archive
The Colliery Engineer
The Colliery Guardian
Mine & Quarry Engineering
Mining Journal
The Science and Art of Mining
Coal Magazine
Coal News
Coke and Gas
Coke and Gas - Main Index
Coke and Gas - Subject Index
Master Name Index
What's new in the site
Mining
Mining History
Colliery Index
Colliery Maps
Company Overviews
Who's Who
Mineral Information
Managers Certificates
Educational Material
Bibliography
Statistics
Workers/Employee Lists
Notes for Family Historians
War Service information
Disasters
Disaster Reports
Names of those killed
Disasters in the 1700s
Disasters in the 1800s
Disasters in the 1900s
Memorials
Awards for Gallantry
On this day ...

Links to other sites of interest
Industrial Heritage Days Out
Former www.pitwork.net web site

Index to site

Contact and address details

Share Page with Social Media

Share on Facebook

Share with Reddit

Share on Delicious

Title Prev Page Return to Index Next Page Title
 
 Coke and Gas August, 1959 

Coke handling and screening

After quenching, the coke car is run to the inclined coke wharf where the coke is discharged. The coke wharf is 150 ft. long and of reinforced concrete surfaced with hard-burnt blue bricks. The regulating gates through which the cooled coke is fed are of steel and are hand operated from a platform extending the length of the wharf. This platform is protected by a concrete canopy.

The coke wharf conveyor (see Fig. 13) is a 36-in. belt conveyor (1) capable of delivering 75 tons of run-of-oven coke an hour on to a 36-in, belt conveyor (2) which elevates it to the primary screen in the coke screening station. This is a single deck vibrating screen separating the coke at 2½-in.

Oversize coke from the primary screen is delivered by chute either on to a 36-in, belt conveyor (3) which in turn delivers it to a 42-in. 'large coke' boom loader (4) for discharge into rail wagons, or to a coke cutting machine. The coke cutter has a capacity of 50 tons an hour and reduces the coke in size to below 2½ in.

Undersize coke from the primary screen plus coke from the cutter, or run-of-oven coke from a chute bypassing the screen, is discharged on to a 36-in, belt conveyor (5) which elevates it to a transfer station where it is delivered to a 36-in, belt conveyor (6). This in turn passes the coke to a second transfer station, where it is received by a 36-in, belt conveyor (7) and delivered back into the screening station. Here it is discharged, either direct or via a second coke cutting machine, on to the secondary screens.

There are four secondary screens, the first being a single deck vibrating screen separating at 1½ in., which passes the oversize coke via a chute to a hopper beneath, and the undersize to a second screen. This second screen is also of the single deck vibrating type which screens out the breeze (0-3/8 in.) and delivers it to the breeze compartment below. The remaining fraction is passed to the first of two reciprocating grading screens arranged in line above the hoppers. These are both of the double tray balanced type and grade the coke into the following sizes: 3/8 in. to 5/8 in.; 5/8 in. to ¾ in.; ¾ in. to 1 in. and 1 in. to 1½ in. for delivery direct into their respective compartments in the storage hopper.

The screening station is a combined structure accommodating the primary and secondary screens, the coke cutters and the six coke hoppers. It is of steel-framed construction clad with asbestos-cement panel sheets. The coke hoppers are also of steel and are lined with Gunite. The five main compartments have a storage capacity of 30 tons each, and the breeze compartment a capacity of 17 tons. Discharge gates and outlet chutes are provided so that each grade of coke, with the exception of breeze, can be delivered over debreezing screens either on to a 42 in. 'domestic-coke' boom loader (8) feeding rail wagons or direct to road lorries. Alternatively, on the road loading side, the coke can be passed to either of two weighing and bagging machines on the bagging platform. The breeze from the hopper is delivered by chutes to rail wagons and road lorries, and that from the debreezers to road lorries only.

A complete dust extraction plant is situated at one end of the screening station. Coke dust is extracted from all the various screens and chutes and conveyed by a system of ducting to a Rotoclone and is subsequently hoppered.

To deal with coke returned from the ground store a reclaimed coke wharf is provided. From the wharf the coke is fed through discharge gates on to a 36-in. belt conveyor (9) which passes it through a reinforced concrete tunnel under the railway tracks and delivers it on to belt conveyor (2), prior to entering the screening station at the primary screen. The reclaimed coke wharf is 6 ft. long, constructed of reinforced concrete and surfaced with hard-burnt blue bricks. A separate conveyor and hopper is being installed to permit run-of-oven coke from the wharf belt to be put direct into stock.

Rail wagons receiving coke from the two boom loaders are marshalled by means of two Wagontrolers which automatically move the wagons into position under anti-spillage chutes at the head of the boom loaders. The Wagontroler equipment, the loading and weighing operations, and indeed the entire coke handling and screening system is controlled from a central desk.

The centralised instrumentation and control systems

The outstanding feature of the Murton coking plant is the centralised instrumentation and control systems provided for the operation of the byproduct and benzole plants and the coal and coke handling plants. They provide a degree of near automation never before attained in the working of a coking plant and have resulted in an appreciable reduction in the number of operators required.

Coal handling control. The coal handling plant control desk is located in a dust-free air conditioned room beneath the blending bunkers. The desk incorporates an illuminated mimic diagram panel which records all the information necessary for the required operation of all machines and conveyors from the delivery of washed coal at the blending bunkers until it is discharged into the ovens bunker. The panel shows which conveyors are running, the position of all flygates, and the amount of coal stored in the various bunkers. Bunker-full indication is obtained by the use of Fielden Tektor electronic level indicators.

Stopping and starting of the coal stream is controlled from switches incorporated in the desk. Before any item can be started up a series of warning bells are sounded in the vicinity of the items to be started. These bells ring for an adjustable predetermined period, after which the plant can be started in the correct order according to the setting of the flygates, the positions of which are given by appropriate illumination on the mimic panel. The control switches are variously coloured to differentiate between the sections of the plant.

The desk also contains the high-tension circuit breaker controls and indicators for two crusher motors although only one of these is in use at present.

Coke handling control. A similar dust-free air conditioned room for the coke handling plant control desk is located above the Wagontroler and weighbridge gear house at the screening station. The desk is provided with a diagram panel and various indicator lamps to show which sections of the plant are in operation and whether the coke hoppers are full or empty. High and low level indication for the hoppers depends upon gamma rays obtained by using suitably positioned and shielded Cobalt 60 radio-active isotopes accommodated between the sides of the coke bunkers and the adjacent walls. The electronic equipment is Isotope Development's Gamma Switch.

By remote pushbuttons, differentially coloured control switches and a system of warning bells, similar to the coal handling control, the operator can supervise the correct sequence operation of the whole of the handling and screening system. The desk also incorporates means for controlling the Wagontrolers at the boom loaders, and for marshalling, weighing and loading of empty wagons and weighing and marshalling of full wagons.

Coke pushing control. The pushing operation at the coke ovens is controlled by the W-D Gamma Interlock system, which depends upon a gamma beam passing from the coke guide to the pusher machine through the oven space above the charge. The system automatically ensures that the charge cannot be pushed until both doors have been removed and the pusher machine and coke guide correctly aligned with the oven. The apparatus consists basically of a transmitter and a receiver. The transmitter unit, mounted on the coke guide, is a solid steel container housing a Cobalt 60 isotope and is provided with a shutter actuated by a hydraulic thruster. When the shutter is opened, a gamma beam passes through the oven roof space and impinges on the geiger counter receiver mounted on the pusher machine. The receiver, which is of special design incorporating a 'fail safe' device, is fitted with a relay which is actuated by radiation and thus closes a master switch on the 'ram forward' travel power circuit.

Emergency stopping of the pushing operation can be effected by either of two methods, both of which are instantaneous. The first consists of a pushbutton control on the coke guide which closes the shutter on the transmitter. The second is a ram stop device incorporated on the coke car locomotive, which works on the principle of injecting a high frequency signal into the overhead power lines. This signal is picked up by the overhead power lines of the pusher machine and causes a relay to operate in the ram forward circuit.

The coke locomotive, coke guide and pusher machines are also equipped with the B.T.H. Clearcall 'intercom' system. This works on a similar principle to the ram stop device, i.e. the injection of high frequency signals into the overhead power lines. The ram stop and Clearcall systems operate on specially selected frequencies to avoid interference with each other.

The pusher machine is operated from an armchair unit from which all the electric motors on the machine are controlled. So far as is known this is the first time that this type of control unit has been fitted to a pusher machine.

Byproduct and benzole plants control. This is the principal control system and is described in detail after the sections dealing with the byproduct, benzole and other ancillary plants.

Producer gas plant

Producer gas, for diluting the surplus coke-oven gas to a suitable calorific value for town use, is manufactured in two Gibbons Heurtey H.W.J. 18 gas producers. These are 4 ft. 11 in. in diameter and of sufficient capacity to serve the present plant and also the future extension. The producers, together with the overhead coke bunker, are housed in a steel framed building the upper portion of which is asbestos sheeted and the lower portion brick panelled on three sides.

Coke for the producers is stored in a 7 tons capacity reinforced concrete hopper, from which it is discharged into a coke skip and elevated by an automatic skip hoist to the storage bunker above the producers. Each producer is provided with a double sealed hand charge hopper through which the coke is fed into the generator, the upper portion of which is firebrick lined and the lower portion, or reaction zone, water jacketted. Ash is discharged through a mechanical grate and motor driven ash pan. Two motor driven air blast fans, complete with automatic governors, maintain constant air pressure in the producers.

Producer gas cooling and washing. Equipment provided for cooling and washing the producer gas consists of two steel pre-coolers each superimposed above a washbox, two motor driven gas washing fans with provision for a third, two spray separators, and a 7 ft. diameter mild-steel gas scrubber.

Water from the gas washing apparatus is received in a water sump divided into two equal compartments of 3,000 gal. each. One compartment receives the washing water, and the other receives water from the benzole plant intercepting sump, treated waste liquor from the water treatment plant, and raw water makeup. Three motor driven centrifugal pumps, each with a capacity of 6,000 gal. an hour, are provided to pump water (a) from the first compartment to the gas washing apparatus and (b) from the second compartment to the quenching station. The third pump acts as a common standby for both operations.

Gas collecting system

The crude gas leaves the ovens through ascension pipes on the pusher side of the batteries and passes into the gas collecting mains, there being one to serve each battery. At the adjacent ends of the collecting mains there are two gas off take mains which connect into a common suction main spanning the pusher track and terminating at the downcomer before the primary coolers.

One ascension pipe is provided for each oven. It consists of a refractory lined mild-steel stand pipe and cast-iron return bend with inspection hole and cast-iron cover. The return bend is fitted with a spray for liquor flushing and a steam connection for use during the coal charging operation. A hand operated cast-steel liquor-sealed dish valve is provided between each return bend and the collecting main.

The collecting mains have liquor sprays positioned at every alternate oven and each main is complete with a liquor-sealed bleeder and a pitch trap.

Constant pressure in the collecting mains is maintained by two gas pressure regulators, which consist of a butterfly valve in each offtake main controlled by an Askania regulator.

The return flushing liquor and the accompanying heavy condensates from the pitch trap of each collecting main drain through the suction main and downcomer to the liquor flushing and separating tank.

Ammonia liquor and tar services

There are two pumps which deliver the flushing liquor to the ascension pipes and collecting mains, and transfer liquor to the ammonia washers. They are of the centrifugal type, one driven by an electric motor and the other by a steam turbine. Each has a capacity of 60,000 gallons an hour and provision has been allowed for the addition of a second motor driven pump of similar capacity when the plant is extended. Two liquor strainers are provided to filter the flushing liquor after leaving the pumps.

The liquor flushing and separating tank, which separates the tar before recirculation of the ammonia liquor, is of the mechanically operated scraper type with a 45 deg. slope at the inlet end and a decanting capacity of 34,000 gal. It is divided into two compartments each provided with a scraper conveyor for the continuous removal of residue, which is discharged through heated outlet hoppers via sludge valves. Tar from the separating tank overflows into a 5,000 gal. receiving tank, whilst the liquor is decanted into a tank of 10,000 gal. capacity.

A three-compartment reinforced concrete sump receives the liquor from the ammonia washers, and hot and cold condensate from the primary coolers and byproduct apparatus. The strong liquor compartment has a capacity of 4,500 gal. and the hot and cold condensate compartments a capacity of 3,000 gal. each. From the cold condensate compartment tar is transferred, by means of a tar leg, with adjustable sleeve, to the hot condensate compartment, and decanted liquor overflows to the strong liquor compartment.

There are four steam driven Duplex type tar and liquor pumps located in the central byproduct plant building. Each has a capacity of 6,000 gal. an hour. One pump serves the hot condensate compartment of the liquor sump, transferring liquor and tar to the liquor flushing tank. A second pump transfers tar from the tar receiver to the two 150,000 gal. tar storage tanks and is also used for tar loading. A third pump delivers liquor from the strong liquor compartment of the liquor sump to a strong liquor storage tank, whilst the fourth pump serves as a common standby.

Gas cooling, exhausting and tar extraction

Primary coolers. From the downcomer the gas passes to the primary coolers for cooling by indirect contact with water. The coolers are of the tubular type and stand on an elevated concrete plinth which forms part of the central byproduct plant building. There are three coolers, two normally in operation with one a standby, and each is provided with seal pots for the collection of condensate into high- and low-temperature fractions. Provision has been made for the accommodation of a fourth cooler in the future.

Exhausters. Two turbine driven gas exhausters of the two-stage double flow type are provided to withdraw the gas from the ovens and primary coolers, and to discharge it through the byproduct equipment.

The exhausters are of Richardsons Westgarth manufacture and one is normally in operation with the other a standby. Each is capable of handling the total make of gas from the present plant and the future extension. A maximum volume of 874,000 cu. ft. of gas an hour can be passed by each exhauster, delivering against a back pressure of 2 lb. per sq. in. Each exhauster is direct-coupled to a high speed impulse type steam turbine operating with normal steam at 150 lb. per sq. in. and exhausting against a back pressure of 15 lb. per sq. in.

Tar extractors. The gas is delivered under pressure to the Whessoe W-D electro-detarrers which are located on the plinth adjacent to the primary coolers. Immediately beneath, in the enclosed portion of the byproduct building under the plinth, are the high tension rectifiers operating the detarrers. There are three detarrers of the vertical tube, suspended wire electrode type, each 6 ft. 6 in. in diameter. Normally all three detarrers are in operation, but when necessary any two of the units are capable of handling the normal gas load without loss of efficiency. There is provision for a fourth detarrer when the plant is extended. Each detarrer is connected to its own transformer rectifier set, although any two of the three rectifiers are capable of supplying sufficient potential for the operation of all three treater units if necessary.

Secondary cooler. To cool the gas before it enters the ammonia washers and for naphthalene removal, there is a secondary cooler using petroleum oil as the cooling medium. The cooler is hurdle filled, elevated on a concrete plinth, and is fitted with a mist eliminator and facilities for steaming out. Supported on concrete saddles beneath the cooler, there is an oil decanting tank, of 6,000 gal. capacity, which receives the drain from the cooler and separates the condensed water from the oil. Any benzole in the vapours vented from the tank is recovered by a vent scrubber fitted with ceramic rings and irrigated by an oil bleed from the pressure line serving the secondary cooler. The circulating oil is cooled by indirect contact with water in a range of six floating-head tubular heat exchangers, operating in series. Two further units will be added when the plant is extended. From the decanting tank, oil is delivered back to the cooler via the heat exchangers by one of two centrifugal pumps, the other being a standby. Each pump is direct coupled to an electric motor and has a capacity of 45,000 gallons an hour.

Liquor recovery

Ammonia washers. The cooled gas passes to three Whessoe ammonia washers, operating in series, although if necessary any one unit can be bypassed as the remaining two are capable of handling the normal gas load. The washing medium is normally filtered waste liquor from the concentrated ammonia liquor plant, but soft treated water can be used in the last bay of each washer, and provision has been made for the possible introduction of cooled weak fixed liquor as an alternative medium. Each washer comprises a single unit of four washing chambers with four centrifugal pumps to circulate the washing medium. The ammonia liquor leaving the washers gravitates to a strong liquor sump, whilst any moisture entrained in the gas is trapped in a vertical downflow water separator placed in the gas main before the benzole scrubbers. Provision has been made for duplication of the washers when the plant is extended.

Liquor coolers. Four floating-head liquor coolers are used to precool the waste liquor before it enters the washers. The arrangement is such that if and when virgin liquor is to be cooled, two coolers will operate on waste liquor and the other two on virgin liquor. Any one cooler can be isolated for cleaning and maintenance, and there is provision for the future installation of two further units.

Drawings and Photographs accompanying the article

 

Prev Page Return to Top of Page Next Page

 

mail
Mail:
Webmaster
Back
Back
Home
Home
Open Government Licence   Contains public sector information licensed under the Open Government Licence v3.0.

Copyright © 1999-2024 by The Durham Mining Museum and its contributors
Registered Charity No: 1110608
Page last updated: 31 Dec 2022

Privacy Policy
 
Terms & Conditions
 
Search
Search
Print
Print