Report On The Causes Of, And Circumstances Attending, The Explosion Which Occurred At Cambrian Colliery, Glamorgan, On 17th May, 1965.
The Right Honourable Frederick Lee, M.P.,
Minister of Power.
Sir,
In accordance with your direction, I held a Public Inquiry with respect to the accident which occurred at Cambrian Colliery in the County of Glamorgan on 17th May, 1965. The names, ages and occupations of the 31 persons who were killed and the one person seriously injured in the accident are given in Appendix I.
2. I opened the Inquiry in the Law Courts, Cardiff, on 19th July, 1965, and it lasted four days, during which fifty-eight persons gave evidence. Their names and occupations are given in Appendix II.
3. The interested parties were represented as follows :—
- The Ministry of Power, by Mr. Cyril Leigh, H.M. Divisional Inspector of Mines and Quarries for the South Western Division, with Dr. E. M. Guenault, Deputy Director of the Safety in Mines Research Establishment.
- The National Coal Board, by Dr. H. L. Willett, Deputy Director General of Production (Safety and Techniques), with Mr. G. S. Morgan, Production Director of the South Western Division of the National Coal Board, and Mr. G. Blackmore, Area General Manager of the No. 3 Area in that Division.
- The National Union of Mineworkers, by Mr. W. Whitehead, President of the South Wales Area, with Mr. L. James of the Union's Safety Department in the Area.
- The National Association of Colliery Overmen, Deputies and Shot firers, by Mr. E. White, President of the South Wales Area, with Mr. W. D. Jones, District Secretary, and Mr. M. Harcombe, Lodge Secretary, Cambrian Colliery.
- The National Association of Colliery Managers and the British Association of Colliery Management, by Sir Andrew Bryan, Mining Engineer, with Mr. W. Humphrey, Electrical Engineer, and Mr. J. Pocock, Mining Engineer.
4. My findings are that :—
| | (1) |
the casualties were caused by an explosion which occurred just before 1.00 p.m. in the P. 26 District in the Pentre Seam;
|
| | (2) |
the explosion was almost entirely one of firedamp, flame spreading along about 325 yards of face and return roadway and coal dust playing no significant part;
|
| | (3) |
the firedamp involved was emitted into the airway from strata other than the seam being worked and assumed explosive proportions because of a severe reduction in the ventilation circulating the district;
|
| | (4) |
this reduction resulted from a prolonged short-circuit through two access holes in an air bridge (or air crossing) and from a connection with previous workings; and
|
| | (5) |
the firedamp was ignited by an electric arc within a gate-end switch, which electricians were testing while the front cover was unbolted.
|
|
|