A linesman was killed at Black Boy Colliery, Durham. Two 3-phase, bare conductor overhead lines, transmitting electricity at 2,750 volts, 40 cycles, and 2,500 volts, 60 cycles, respectively, are carried, one on either side, on "H" poles, and link up three adjacent collieries. The single wooden poles forming the "H" are set at 8 ft. centres. The conductors of each line are disposed triangularly and are attached to insulators on three channel bars bracing the poles near the top. The nearest conductor of one line is about 5 ft. 6 ins. away from that of the other line. Deceased and another linesman were near the top of one side of an "H" pole and engaged in coupling through one of the lines part of which had recently been renewed. All the conductors near the side at which they had to work were made dead, but the opposite line was live at 2,750 volts. Deceased, in order to change his position from one side of the channel bars to the other, attempted to climb up over them, when his foot appears to have slipped, and he fell on to a live conductor of the opposite line. He received a fatal shock and his body was held on the line. He was rescued about 15 minutes later. Artificial respiration was tried unsuccessfully for over 30 minutes.
|
|||||||||||||||||||||||||||||||||
![]() |
||||||||
|