Washington 'F' PitMiscellaneous Notes and IncidentsWashington "F" Colliery, Durham: To repair a fractured cage hoop a welding transformer was brought into service, the 625-volt primary winding being connected temporarily to the incoming terminals of an oil switch in a sheet steel cubicle controlling a compressor. The cubicle had two hinged doors, the lower giving access to the oil switch and the upper to the isolating knife switches which were opened by means of an insulated pole while the temporary connection was made. When the work was finished the electrician forgot to open the isolators, opened the lower door of the cubicle and "flicked" across the switch terminals with a screw-driver, receiving burns on his hand from the resulting arc. The two doors of the cubicle should have been interlocked. Source: Report of H.M. Principal Electrical Inspector of Mines for 1948, from a copy held in the Scottish Mining Museum, Newtongrange, Midlothian
|
![]() |
||||||||
|