At New London Colliery, Nottinghamshire, a coal cutter machine-man, having taken the trailing cable up to the machine ready for cutting, called for the current to be switched on at the gate-end box ; immediately this was done he received a fatal shock. He had called for the current before inserting the pommel in the machine, and before coupling up the extra earthing lead. An examination of the pommel showed that the cable had been partially drawn out, and that the earth lead had been torn from its socket, as had also one of the power leads. This latter, after it was drawn, had made contact with the metal of the pommel. The trailing cable had evidently been subjected to a strain it was never intended to bear, but had the pommel been inserted in the machine and the jumper earth connection made before the current was switched on, no accident would have taken place. The provision of a device of the "Rowley-Williams" type, which renders it impossible for the current to be put on to the trailing cable until both plugs are home and the earthing circuit between the gate-end box and the machine properly closed, would prevent accidents of this kind. The system was three phase alternating, and the pressure 500 volts. Source: 1924 Mines Inspectors Report, North Midland Division (No. 4) by J. R. Felton, H.M. Inspector of Mines [DMM Ref: L-01624 - Tom Bainbridge Collection], Page: 22
|
|||||||||||||||||||||||||||||||
![]() |
||||||||
|