There were two steam-boiler explosions last year, one at Bo'ness, and the other at Motherwell. Both were high pressure boilers, 5 feet diameter, 3/8 in. plates ; the former was 20 years and the latter 15 years in use. It did not appear that either of them had been short of water, and, excepting the worn-out condition of the boilers, there was nothing to account for the explosions. A question arose out of the Bo'ness explosion as to compliance with the 13th general rule, which requires that every boiler shall be provided with a proper steam gauge. The boiler which exploded was one of a range of five boilers all connected together by one steam-pipe. A steam gauge was placed on this steam-pipe, and thus every boiler, when working, had a steam gauge, or was connected with a steam gauge; but the boiler had been "off" getting cleaned, and steam was being raised in it when it burst, so that it was not at the time provided or in connexion with a steam gauge ; nor can any one of a range of boilers similarly situated, at all times comply with the general rule, unless there be a steam gauge upon each boiler. At the suggestion of Crown Counsel I sent a circular to the coal masters in my district, requesting them to put a steam gauge on each boiler. Many of them have already complied, and others are doing so. Source: 1868 Mines Inspectors Report, East Scotland District by Ralph Moore, H.M. Inspector of Mines, Page: 120
|
|||||||||||||||||||||||||||||||
![]() |
||||||||
|