1st November 1941, Page: 133, Column: 1
Mine Ventilation Problems
In the discussion of mine ventilation systems before the Mining Society of Nova
Scotia Mr. W. D. Sheldon, Jnr., said that when selecting a fan to
replace an old one, the resistance that the mine Will develop in passing the
desired quantity of air can be calculated from tests made with the old unit,
but quantity and pressure measurements must be taken accurately, and both the
temperature of the air and the height of the barometer should be ascertained.
The quantity of air passing should be measured at a point where the airway is
of uniform cross-section and where air velocities are reasonably uniform, and,
if such a location is not convenient or available, a 10- to 15-foot section of
the airway should be lined smoothly with boards to form a measuring station.
For measurement of air velocities from 150 to 2,000 feet per minute, the
anemometer will give reasonably accurate results and is to be preferred to
other instruments. For velocities of 2,000 feet per minute and higher, the
pitot tube and manometer are more accurate and therefore should have
preference. Where the quantity of the air to be passed by the new installation
is not more than 20 per cent. greater than that of the old one, the mine
resistance can be assumed to increase as the square of the quantity of air
being passed. Tests in several mines indicate that the actual increase varies
between the 1.5 and 2.0 power of the quantity ; but only with difficulty can
the pressure be measured because of variations in natural draught, leakage, and
other modifying conditions.
Where the new fan is to deliver more air than the fan it displaces, the
anticipated resistance can be calculated as proportional to somewhere between
the 1.6 and 1.9 power of the quantity passed. For this range, the mine
resistance can be calculated, and a fan can be selected under any resistance
condition within it. To ensure long service at high efficiency, the anticipated
minimum and maximum pressure that will be needed to overcome mine resistance
thus likely to be encountered, a fan can be selected that Will operate within
the high-efficiency portion of that unit's performance curve.
 |
 |
|