14th December 1940, Page: 187, Column: 1
Mining Electrical Equipment
Before the London branch of the Association of Mining Electrical Engineers,
Mr. N. V. Castling dealt in his presidential address with some of the
developments in circuit breakers and associated equipment suitable for use in
mines. He expressed the opinion that the tendency is to use air-insulated
control gear in medium-voltage systems inbye, owing to the ease of maintenance.
The air-insulated type allowed easy access for inspection, and the isolators
and other protective fittings were more conveniently added. In mining
switchgear, malleable iron or gunmetal dividing boxes were being favoured
instead of cast-iron. That applied particularly to boxes that could also be
used as straight-through junction boxes, and the object was to prevent
accidents due to fracture of the enclosure. The President stated that plug
interlock had usually been provided by a mechanical attachment on the
circuit-breaker to prevent the removal of the plug when the switch was closed.
That did not prevent the removal of the plug at the feeder end, and it was
becoming more common to provide an electrical interlock, which applied at both
ends. That necessitated a 5-core instead of a 4-core cable. A typical scheme of
remote control for conveyors and coal-cutters was to provide a substantial
contactor with the necessary protective devices fitted in a flameproof case,
the contactor being controlled by a low-voltage pilot circuit (30 volts
maximum) operating over pilot conductors embodied in the cable to the motor or
over separate pilot wires. The pilot circuit needed special consideration, and
should be intrinsically safe and arranged to open the main circuit in the event
of a short-circuit of the pilot wires in any place other than the pilot switch.
 |
 |
|
Names mentioned in this article
|
 |
 |
| Name | Age | Occupation | Notes |
| Castling, N. V. | | President | |