6th May 1939, Page: 346, Column: 1
Underground Fire Extinction
By Superintendent F. J. Johnston, M.I.M.E.
The fire-fighting regulations refer to three classes of mines
(1) Mines with less than 30 underground employees (2) Mines
with over 30 underground employees ; (3) Mines with over 100
underground employees. Small mines are those mines with
less than 30 underground employees and are not affected by the
regulations.
At all mines there must be kept ready for immediate use at
appropriate places fire extinguishing appliances as specified.
Appropriate places may be taken to refer to the places which are
considered most suitable for keeping appliances relative to the
main roads and working places. At these places a supply of
suitable dust and portable fire extinguishers meet the requirements.
Portable extinguishers may include the 2-gallon type
of extinguisher.
Alternatively to the method of protection just referred to a
small hand pomp and a supply of water may be provided.
Where an ignition of gas is liable to be produced in the cut of
a coal-cutting machine some provision has to be made for preventing
such an ignition or extinguishing an ignition should it
occur. First of all it will be necessary to decide whether inflammable
gas has been or is liable to be ignited in the cut. It
is difficult to say how such a fire can be extinguished, and it is
doubtful as to what might be considered an effective means to
prevent ignition.
Fire extinguishers (kept in pursuance of the regulations) must
be examined, discharged and refilled as often as may be necessary.
This does not necessarily mean that the extinguisher must be
operated. It will be sufficient if the contents are taken out
and examined and replaced periodically.
Fire extinguishers which are liable when operated to give off
poisonous or noxious fumes are forbidden for use underground.
This includes carbon citrachloride (CTC) and methyl bromide
types. Pure CO 2 gas extinguishers are not included in the
forbidden list.
At mines with over 100 employees underground there shall be
kept where a fire is liable to occur : (a) A supply of water ; (b)
Means of conveying the water; (c) Manual force pumps and
appurtenance manual pumps of from 5 to 10 gallons per minute
capacity with sufficient water to maintain a jet for 30 minutes
may be suitable.
Once every month a competent person, who may be any suitable
person appointed by the manager, shall make an examination
of the equipment and material.
Rules for the organisation and conduct of fire-fighting work and
drills shall be adopted and enforced by the manager. This simply
means that the colliery workers shall be capable of using the
appliances provided, know where to obtain them, and generally
what to do in case of fire.
Methods of Extinction.
There are three main principles involved in extinguishing a
fire which may be used individually or combined to produce
extinction: (1) Cut off the supply of air; (2) Cool the burning
material down to a point which is below the ignition point of the
material; (3) Make a break in the combustible material which
prevents the fire extending for want of material to burn.
Smothering is an example of the first principle, but can obviously
only be applied to fires of small extent. To cut off the air supply
to a large fire in a mine is a matter often involving many difficulties
and complications.
To apply the cooling principle of fire extinction, water has been
found to be the most suitable medium to use for this purpose.
The reasons for this are : (a) Water and its vapour are incombustible.
(b) Water will extract more heat, weight for weight,
than any other substance, i.e., its thermal capacity is greater.
(c) Water is converted into steam. The quantity of heat required
to convert water at boiling point into steam is about six times that
required to raise the water to boiling point. The cooling effect
of converting water into steam is therefore extremely great.
(d) Water ejected at a pressure has an additional beating out
effect. (e) The steam and water vapour produced also act to
some extent as a blanket to shut off air from the fire.
The chief action, of water, however, is its cooling powers.
It should be borne in mind, and the fact is not always realised,
that, if large quantities of water are thrown on to a fire in a short
period of time, large volumes of steam will be produced hampering
access to the fire and preventing removal of the material which
has been cooled.
One gallon of water will produce 265 cubic feet of steam; 100
gallons per minute for 10 minutes will produce 265,000 cubic
feet of steam.
The quantity of water capable of being used is usually governed
to some extent by the available space adjacent to the fire and
the ventilating current passing through the fire.
The volume of smoke produced is also a factor to be considered
in extinguishing fire in mines. The greater the quantity of oxygen
supplied to a fire the less will be the quantity of smoke produced,
but the temperature of combustion will be greater and the fire
increase in intensity. A line of demarcation must therefore be
drawn in deciding how much air can be admitted to a fire. If
sufficient water is available the general policy would be to regulate
the ventilation on the fire sufficient to clear the smoke and allow
water to be delivered at effective range.
While water still remains the most important fire extinguishing
agent it is not always obtainable in sufficient quantity, or desirable
in mines that large quantities are essential at one time. The
importance of dealing with fires in their incipient stage therefore
becomes more evident. The water used must be delivered at a
pressure and judiciously with effect upon a fire.
There are three main principles employed in fire appliances
to achieve this object: (1) By chemical action ; (2) By compressed
gas; (3) By the use of pumps.
Fire-fighting Regulations.
The foregoing notes have reference to the General Regulations
made on 8th August, 1938, which read as under :—
(1) (a) In every mine, other than small mines which are
naturally wet throughout and mines of stratified ironstone, there
shall be kept, ready for immediate use, at appropriate places in
relation to each working face and along the main roads, a sufficient
supply of suitable dust or sand and of portable fire-extinguishers,
except in so far as water is provided at these places with equipment
to serve the same purpose.
(b) At each place where dust, sand, or water is so kept, means
shall be provided for readily conveying the material by hand and
for using it for fire-fighting.
(c) At all times when a coal-cutting machine is in operation
at any working face in which an ignition of inflammable gas has
been, or, having regard to the nature of the strata, is liable to be,
produced in the cut by its operation, effective means to prevent
such ignition shall be provided on the machine, or a supply of
suitable dust or sand in a proper container, or a portable fire-extinguisher
shall either be carried on the machine, or, if that is
impracticable owing to the thinness of the seam, shall be kept at
suitable intervals along the working face and at the roadhead
at the intake end of the working face.
(d) Fire-extinguishers shall be examined and discharged and
refilled as often as may be necessary to ensure that they are kept
in good working order.
(e) Fire-extinguishers which are liable, when operated, to give
off poisonous or noxious fumes shall be provided or used underground.
(2) At every mine at which 100 or more persons are employed
underground there shall also be provided and kept ready for
immediate use — (a) a supply of water sufficient for the purpose
of fighting fires underground and, (b) efficient means of conveying
the water and delivering it promptly at adequate pressure and in
adequate volume to all parts of the mine in ordinary use for
working or travelling where fire is liable to occur. Except in
so far as provision is made so to deliver the water through pipe-lines
and hose extensions, it shall be so delivered from water tanks
or barrels by portable force pumps and all equipment necessary
for this purpose shall be provided and kept constantly ready for
use. Provided that the Inspector of the Division may exempt
from any requirement of paragraph (b) of this Regulation any
mine, or part of a mine, in respect of which he is satisfied that it
is not reasonably practicable for the owner to comply with the
requirement.
(3) Once every month all the equipment and material provided
for fire-fighting shall be examined by a competent person appointed
for that purpose who shall report in writing to the manager
of the mine and shall specify in the report anything that he
considers to be defective or lacking.
(4) The manager of every mine to which No. 2 of these
Regulations applies shall adopt and enforce rules for the organisation
and conduct of fire-fighting work and of fire-drills.
* From paper on "Underground Fire Extinction. with special
reference to Fire-fighting Regulations (1938)," read at the April
meeting of the Associates and Students' Section of the North of
England Institute of Mining and Mechanical Engineers. Mr. Johnston
is superintendent of the Durham and Northumberland Collieries
Fire and Rescue Brigade (Elswick).
 |
 |
|