26th February 1938, Page: 265, Column: 1
Firedamp Recorders
In his paper on "A Distance Recorder for Firedamp," read
before the Midland Institute of Mining Engineers, Dr. H. Lloyd,
M.Eng., recalled that several years ago the Safety in Mines
Research Board was asked to try and produce an instrument
suitable for use underground, which would record continuously
the percentage of firedamp in the air in its neighbourhood, and
experiments were made at the Sheffield laboratories of a firedamp
recorder which fulfilled the conditions. The principle which was
adopted was the straightforward mechanisation of a common
method of gas analysis, as carried out manually in, for example,
the Haldane apparatus. The same principle has been retained
in later S.M.R.B. recorders. A continuously acting pump connected
by a pipe-line to the place from which the air is to be taken,
delivers the air to a thick-walled cylindrical brass chamber of
about 15 c.c. capacity. The chamber has three ports, which are
opened and closed by valves working from a camshaft. In the
first of the five stages in the cycle of operations the inlet and
exhaust valves are open and a quantity of the air to be tested
is passed through the chamber, sweeping out the waste gases
remaining in the chamber from the previous cycle, until it is
filled with the fresh charge. To do this effectively requires about
100 c.c. of air. In the second stage with the inlet valve closed
the other two valves open for a brief period to allow the contents
of the chamber and aneroid to recover from any slight adiabatic
effects and assume atmospheric pressure. In stage three with
all the valves closed and the platinum wire heated to incandescence,
any methane in the sample of air is converted by combustion to
carbon dioxide and water vapour. During stage four the contents
of the chamber are cooling, the thick metal walls of the chamber
acting as a large heat-sink in place of the constant temperature
water jacket customary in laboratory apparatus, but hardly
convenient to use under the conditions imposed underground.
In the final stages the aneroid valve is opened, and the reduction
of pressure resulting from the combustion of the methane is
indicated by the pointer of the aneroid, and recorded on a chart
calibrated in terms of percentage of firedamp. The chart is
driven by clockwork at the rate of inch per hour, and the
deflection of the pointer at the appropriate moment during each
cycle is registered as a dot on the chart by a mechanically operated
striker and an inked thread. The dotted line forms a permanent
record of the percentage of firedamp, any variations in the quantity
appearing as undulations in the line.
Dr. Lloyd said the application of remote indication to firedamp
recorders is a development which suggests itself naturally when
one considers the reasons for the extensive adoption of remote
supervisory control in numerous other industrial fields, such as
steam-boiler plant practice and furnace pyrometry. The Author
further said that an extension of the principle of remote indication
may be used to control an alarm which comes into operation if
the firedamp percentage exceeds some agreed value. An
additional contact spring on the pointer of the transmitting
instrument can be made to close a circuit when the deflections
correspond to more than a certain percentage, causing an alarm
to be actuated, or the gate-end switches to be opened. By using
a stepped relay to operate the alarm circuit, it can be arranged
that all the chambers of the recorder must be in agreement as
to the amount of gas present before the alarm circuit is closed,
thus reducing to a minimum the chances of undesirable consequences
arising from false alarms due to momentary fluctuations
in gas percentage.
Demonstrating the firedamp recorder Dr. Lloyd said at the
outset that it was not suggested the instrument should take the
place in any way of local firedamp detectors or the simple flame
lamp. At present it was rather a survey instrument. Much work
still remained to be done in the search for the complete solution
of the problem. Experiments in developing devices for firedamp
detection have been attended with varying degrees of success.
Many discoveries of recent years, mainly in the realms of physics —
as for example electronics and photo electricity — had offered
promises of providing new and better means for actuating the
final indicator of a firedamp detector, but until some property
of methane as yet unknown was discovered, it was only by improvements
in the application of known principles that progress
would be made towards the attainment of a perfect warning
device.
 |
 |
|