13th March 1937, Page: 277, Column: 2
Boiler Plant Instruments
At the February meeting of the North Staffordshire Institute
of Mining Engineers Mr. J. Vickers submitted a paper on "Power
Economies as Applied to Collieries," and he said that, providing
a fuel, be it waste product or otherwise, contains sufficient heat
units to justify handling, there is no difficulty whatsoever to-day
in obtaining boiler plant of a type suitable for burning it usefully
in steam raising. Discussing boiler plant efficiencies he proceeded
to say that in many cases there is no apparatus on the boiler
excepting the usual steam gauge and safety valve to indicate that
any change in the load has taken place. If the boilers were
equipped with steam flow meters they would indicate instantly
any change which took place and thus give the fireman ample
warning and enable him to maintain the thermal balance of
the boiler plant. This might appear to be a very minor point,
but in the course of twelve months it is possible for a considerable
quantity of fuel to be wasted, and this in itself (in a reasonably
large plant) would more than justify the installation of a steam
flow meter.
Draught Gauges. — In order to ensure that the correct amount
of air is being supplied to the fuel bed, it is essential that "draught
gauges" be fitted to each boiler. Where only one gauge is fitted
to each boiler, it is generally found that the best position is in the
furnace directly over the fuel bed. In this position the gauge is
constantly under the observation of the fireman, and by careful
observation both in regard to water-gauge, thickness of fuel bed
and type of fuel being used, the fireman should be able to judge
the most suitable position for the dampers, and thus ensure the
maximum possible efficiency under all conditions of load. Draught
gauges are usually fitted to indicate the water-gauge at the bottom
of the chimney or in the main flue, but whilst the indications at
these points may serve a useful purpose, they give very little
information in regard to the conditions of draught at the furnace.
It is not uncommon to find boiler plants in operation with the
dampers in one position, irrespective of the nature of the load and
type of fuel. Consequently, when the boilers are operating on
light load an excessive amount of air is drawn through the thin
fuel bed, resulting in the cooling down of the furnace and the
carrying away by the flue gases of a considerable amount of heat.
CO2 Recorders. — There is no better method of obtaining
an
immediate indication of any incidental changes in the efficiency
of the boiler than by the continuous recording of the CO2 content
of the flue gases. Referring to tests carried out by Mr. D. Brownlie
on Lancashire boilers, the average percentage of CO2 on seventy-
five colliery boilers tested is given as 8 per cent., and thus it will
be seen that there was an average fuel loss of 22 per cent. Assuming
that, say, 10 per cent. CO2 is the maximum average percentage
that could possibly have been achieved, this would have resulted
in a net saving of 4 per cent. Again, assume that one of the boiler
plants was consuming, say, 850 tons of coal per week; then the
net saving would have been 14 tons of coal per week, or 700 tons
for 50 weeks, and assume the market value of the fuel used was
10s. per ton, then the value of the fuel saved would have been
£350 per year.
Temperature Recorders. — It is also very necessary for the
temperature of the feed water and flue gases to be constantly
recorded in order to keep a check on the chimney losses, etc.
Assume a boiler to be operating normally with 60 per cent. excess
air, and an exit flue gas temperature of 500 degrees and without
economisers or air preheaters. If economisers were fitted to the
above boiler and the heat extracted from the flue gases and the
temperature dropped to, say, 350°F., then the overall thermal
efficiency (neglecting the incidental power consumption of
economiser motor) would be increased by approximately 58 per
cent.
 |
 |
|