22nd September 1928, Page: 70, Column: 1
Electricity In Mines
By E. L. Martheleur.
[At the annual meeting in June of the Mining Society of Nova Scotia,
Mr. E. L. Martheleur, the chief electrical engineer of the British Empire Steel
Corporation, had for the subject of his paper "Electricity in Coal
Mines." Extending to some fifty pages of the Bulletin of the Canadian
Institute of Mining and Metallurgy, the paper dealt with the question
particularly with reference to the Nova Scotia regulations. An excerpt is
appended.]
The use of electricity in coal mines dates almost from the time when it was
realised that it could be used to produce mechanical power. The first motor put
in service underground was installed to drive a small pump nearly 40 years ago,
and since then the use of electricity in mines has reached an extent undreamed
of at that time. We now find its universal adoption in all the mining countries
of the world. Great progress has been made in the development of mining
electrical apparatus in the last decade, and excellent and adequate material is
now available for the use of electricity underground. Although mining
accidents, due to the use of electricity, are not frequent, the miner is
justified in demanding that all electrical apparatus for installation below
ground be constructed with a greater degree of safety than that used on the
surface. That this view is shared by the authorities of the different mining
countries is evidenced by governmental regulations relative to the use,
erection, and maintenance of electrical apparatus below ground.
The potential dangers of electricity in coal mines are : Shock or burns by
contact with live parts. Shock or burns by contact with parts which, although
normally dead, have become accidentally alive. Fire. Explosion of gas or coal
dust. Explosion of apparatus.
Shocks. — To prevent accidental contact with live parts it is now
general practice to cover all these parts with metal maintained at earth
potential by efficient grounding. Metal-clad switchgear is in universal use in
collieries and it is significant that designs prepared and developed for
difficult service in mines have been accepted in good practice as good
standards for other industrial purposes.
Metals which are normally dead may become charged by accidental contact with
live parts, and it is important to maintain the insulation of these live parts
in an efficient state and to provide adequate spaces between live and dead
metal. Electric cables must be left with sufficient slack to allow for strata
movement, and they must be adequately supported. The armouring of such cable
must be firmly secured to the various apparatus to which they connect, to take
any external forces to which the table may be subjected ; and all dead metal,
such as armouring of cable, frame of motor, and casing of apparatus, must be
kept at earth potential by connection to earth plates and by maintaining
continuity and high conductivity of the grounding system.
Fire. — The second source of danger from the use of electricity in
mines is fire. This may be caused by failure of insulation, by overheating of
conductors, or by electric discharge igniting oil in switches or in
transformers. Even a small fire is extremely serious in a mine. Air which
ventilates the colliery may be quickly mixed with fumes to such an extent that
persons may be asphyxiated in a very short time.
To minimise the risk of fire, attention should be given to the rating of cable,
motors and all apparatus carrying current, and provision should be made to
disconnect any part of the plant which is dangerously overloaded or in which
leakage to ground has taken place. All apparatus containing oil should be of
sufficient strength to resist the effect of an explosion within it (or release
safely the gas produced by such explosion). The oil and mechanism under oil
should be frequently inspected and properly maintained. It is important that
non-inflammable material be used in the construction of rooms containing
electrical apparatus ; oil, waste, and inflammable material should not be
allowed to accumulate at places where electricity is used ; cable and apparatus
should be protected against mechanical damage and located in places where such
damage is least likely to occur.
Ignition of Gas or Coal Dust. — At this date the use of
electricity in places where gas is normally present is not permitted, but there
are many places where gas, although not normally present, may accumulate
whenever the ventilation is not perfect. Air containing a certain percentage of
mine gas is very susceptible to explosion by electric sparking and the use of
flame-proof enclosures is compulsory at every place where gas may be present in
sufficient quantity to be a source of danger. A perfect flame-proof apparatus
is easily rendered defective through carelessness. The omission of a bolt, a
dirty or damaged flange, or failure to secure covers properly, defeat
completely the flame-proof qualities of an apparatus. It should be noted, also,
that an apparatus flame-proof at or below its normal rating may lose its
effectiveness when overloaded or where the ventilation is insufficient to
ensure the proper cooling of this apparatus.
Explosion of Switchgear. — The kind of explosion here referred to
is the explosion of a mixture of air and oil-vapour in the oil containers of
apparatus such as oil circuit breakers and transformers. If the oil is heated
through overloading or lack of ventilation, it vapourises and forms with the
air above the oil level an explosive mixture easily ignited by subsequent
arcing. If the design of the tank is not such as to afford sufficient strength
to resist an internal explosion, or to permit a rapid relief of the pressure
created by such explosion, persons may be injured by projected metal, spraying
of the ignited oil, or a resultant dangerous fire. An explosive mixture is
formed in circuit breakers by sustained arcing between the contacts or when
tripping under heavy overloads. It is important that these conditions be
avoided as much as possible by having tanks of suitable design, strong enough
to resist internal explosion, and by frequent inspection of the mechanism
operated under oil.
It may be in order to explain what is meant by flame- and explosion-proof
apparatus. The term explosion-proof means, I believe, that the container of an
apparatus is made strong enough to resist an internal explosion, and the term
flame-proof means that the apparatus cannot pass any flame or gas into
surrounding atmosphere hot enough to ignite gas or coal dust when an explosion
of the maximum force takes place inside of the container.
To be considered as safe, an apparatus does not need to be enclosed in a
container having sufficient strength to withstand an explosion of the maximum
force if this container is fitted with devices to relieve safely and rapidly
any abnormal pressure within. It is out of the scope of this study to describe
these safety devices ; they are based on the principle of cooling down the hot
gases produced by an explosion to such a temperature that they could not ignite
an explosive surrounding atmosphere. The usual method is to provide the tanks
with flanges 1½ to 2 inches wide and to keep these flanges separated by
.02 to to .01 of an inch. Sometimes rough machined faces to flanged joints,
leaving a slight transverse grooving, is sufficient; sometimes small distance
pieces, .02 inch thick, are riveted to the top flange to maintain the proper
distance between the flanges ; in some devices machined flanges are brought in
close contact by means of relief bolts whose function is to allow the cover to
lift .02 inch to release safely the excess pressure in ease of internal
explosion. When the container is not of great capacity, the different parts are
bolted rigidly together without gaskets and calculated to withstand a pressure
of 150 to 200 lb. per square inch.
Danger, however, is not the only point to be considered in selecting electrical
material for use in coal mines. There are other points of importance, among
which may be enumerated the following :—
All apparatus should conform with the regulations for the use of electricity in
coal mines. These regulations may sometimes appear drastic to coal-mine
operators, but the increment of safety against danger to person and property
repays for the slight increase in capital incurred in the purchase of approved
apparatus.
Electrical apparatus below ground, being installed and worked in remote
locations, seldom if ever receives the same care and attention as equipment
operated on the surface. In fact it is often abused.
Installations underground are always of a more or less temporary nature. As the
mine develops and the work progresses, motor and switch-gears are transferred
from one place to another; as a consequence, a minimum of care is given to the
installation and to the proper housing of this material.
The surrounding atmosphere is often damp, sometimes dusty, or may contain
inflammable gas or coal dust in sufficient proportion to be a source of danger.
The equipment should be designed to meet all these adverse conditions.
The dimensions in the clear of mine roadways are often very restricted, and the
outside dimensions of the various parts of an equipment are specially designed
to suit these conditions. Mining motors are generally long and of small
diameter ; mining transformers are reduced to minimum height and mounted on
special trucks with flanged rollers to suit track gauge for easy
transportation.
For some applications the question of efficiency and power factor is secondary
to securing rugged and reliable motors ; this applies particularly where the
demand is intermittent and the service arduous.
Electrical apparatus below ground is often operated by inexperienced hands,
often abused, and should be made as fool-proof as possible, yet free from any
unnecessary complications.
All apparatus underground should be mechanically protected against mechanical
damage of all kinds.
These considerations and others not mentioned show how the conditions
underground differ from those obtaining on the surface, and explain why
general-purpose apparatus, however excellent it may be for factory or other
industrial works, is totally unfit for iniiung service.
 |
 |
|