2nd July 1927, Page: 387, Column: 1
Automatic Control Devices
Some of the appliances in use at the Valier mine of the Valier Coal Co.,
located in Southern Illinois, are described in Coal Age by Mr. A. F. Brosky.
One example is a power-saving arrangement Which governs the
manipulation of the main hoist while the plant is being operated at 75 per
cent. of its capacity. Valier is a shaft mine working the No. 6 Illinois bed.
The coal is hoisted in skips, and the workings are equipped to produce 8,000
tons in eight hours. At one time this mine held the world's record for
production from a single shaft.
Power is furnished to this mine on a contract, by which a primary charge is
made on a 5 minutes maximum demand and a secondary charge rendered on actual
consumption of energy. With the mine operating at only 75 per cent. of its
capacity, a 15-minute period of grace in each hour allows an adjustment in the
speed of hoisting which limits the load on the entire plant to a fixed maximum.
The main hoist is controlled so as to act like a balancer or flywheel to limit
the over-all load on the plant. This has been accomplished by installing on the
hoist platform, a demand meter and a 5-mlnute clock, both of which are
synchronised with the clock of the power company. They are placed in front of
the operative, who, by watching their indications, can regulate the hoisting
cycles in such a way as to attain the desired end.
The main shaft is 600 feet deep, and each skip has a capacity of 15 tons. The
hoist is driven by a 1,350 h.p. direct-current motor drawing energy from a
flywheel motor generator set which forms part of an Ilgner system of
Ward-Leonard control. This latter machine is itself semi-automatically
governed. When necessary, the hoisting load is decreased or eliminated entirely
by slowing up or stopping the hoist so as to maintain the total plant load at
or below the pre-determined maximum, which happens to be 2,300 k.w. The running
load of the hoist is about 1,100 k.w.
In order to ensure measurements of the same time-interval on both the demand
meter of the coal company and that of the public utility furnishing current,
the latter was requested to replace its spring-driven clock with one that is
actuated by a synchronous motor. This was done, the clock of the power company
being now placed in a common circuit with the demand meter and timer installed
by the coal company. A light circuit from the clock of the power company
flashes a lamp on the hoist platform at the end of each 5-minute period. The
coal company's demand indicator and timer are synchronised with the clock of
the power company by the throwing of a switch upon the flash of this lamp.
The demand indicator in conjunction with the clock on the hoist platform shows
the hoistman what the overall demand of the plant is at all times. A circle
with a radius equivalent to 2,000 k.w. of demand is described on the graphic
chart of the meter. A leeway of 300 k.w. thereby is allowed when the pen
reaches this circle. The operative so regulates the speed of hoisting that the
total consumption at the end of each 5-minute period, indicated by the timer,
never exceeds the 2,300 k.w. of pre-determined maximum plant demand.
These instruments were installed at the beginning of the present year at a
total cost of about 200 dollars. They have cut down the maximum demand by 400
k.w., and have effected a saving in power at the rate of 2,500 dollars per
year.
Another saving, in this case in labour, is being effected through the
installation of a dually-controlled isolated pumping station that delivers
water from a reservoir to the plant. A water-treating installation is operated
in conjunction with this pumping equipment. Should the automatic feature fail,
the whole system can be operated through manual control. At the mine
substation, power is stepped down from 33,000 to 2,300 volts and enters the
building through a three-pole, fused, entrance switch. Thence it is conducted
to an eight-pole, double-throw switch, on one side of which, but located at the
pumping station, is an automatic starter. This energises a 20 h.p. induction
motor driving a triplex plunger pump of 300 g.p.m. capacity. The control
circuit of the automatic starter is operated by the combination of a
water-pressure gauge with an electrical relay, this latter being likewise
installed at the pump station. Coupled with the last-mentioned equipment is a
balancing tank that dampens the effect of pressure surges upon the gauge. The
relay and gauge act jointly to operate the starter when the back pressure in
the water-line reaches either an upper or a lower limit. In case the
automatic-control features should fail, the eight-pole switch can be thrown to
a manual-control circuit containing a three-pole contactor with reclosing
overload relays. The pumping equipment can then be manually operated.
 |
 |
|