4th December 1926, Page: 145, Column: 2
Safety Valves On Steam Pipes
In the Memorandum for 1925 of the Manchester Steam Users' Association by the
Chief Engineer (Mr. C. E. Stromeyer), the following note appears :
"Many steam users have in recent years been troubled with what might be
called pressing suggestions to provide those of their steam pipes which pass
from reducing valves to low-pressure vessels with larger and larger safety
valves, exceeding in some cases the sectional area, of the pipes they were
serving by 100 per cent. The very extremeness of such suggestions makes one
pause, for how can a 2 in. pipe supply enough steam to fill a 3 in. valve to
its full working capacity ? The problem may be dealt with as follows. Assume
that a steam vessel is provided with a short open pipe A, and that facing the
end of this pipe there is the open end of another pipe B, a short distance from
the end of A. Then if the other end of B is connected to a boiler, steam will
impinge on the open end of A and pressure will gradually accumulate in the
steam vessel. What will be the final pressure ? Clearly it will only be
attained when the steam vessel is full, as it were, when no more steam is
flowing into it, and when all the steam arriving from B escapes out of the
space between the two pipe ends, which in this case represents an unloaded
safety or escape valve. The pressure on the end of A and, therefore, also in
the steam vessel consists firstly of such pressure as is to be found at the end
of B, a large portion of the boiler pressure having been used in creating the
steam velocity, and secondly of the reaction pressure of the steam against A.
This is nearly equal to the pressure which created the velocity, so that the
sum of the two pressures is nearly equal to the boiler pressure, the only
reduction being that due to orifice and friction resistance in the B pipe.
Experiments fully confirm this conclusion. During the investigation it was
suggested that much depended on the relative position of the two pipe ends,
that if the B end were enclosed in a chamber in such a way as to act as an
ejector it should be possible to create a vacuum in the A pipe. That view is
correct, but it implies that the discharge opening should be open, and not
closed by a safety valve, and that would mean in practice that if a safety
valve could be devised for working on the ejector principle, some contrivance
would have to be added to remove the safety valve entirely, or at any rate its
load, whenever the pre-arranged pressure was exceeded. Whether this
complication is practicable and whether the creation of a vacuum would not lead
to collapses need not be considered here, but it was deemed desirable to add
one experiment to the series in which the B pipe discharged its steam straight
against the safety valve."
 |
 |
|
Names mentioned in this article
|
 |
 |
| Name | Age | Occupation | Notes |
| Stromeyer, C. E. | | Chief Engineer | |