Oil Fuel For Steam Boilers
With the Memorandum for 1925 of the Manchester Steam Users' Association, Chief
Engineer C. E. Stromeyer has issued a circular referring to the
experiences of members using oil fuel for their boilers, with the following
notes for those already using oil fuel:—
A full supply of air to the burners must be maintained, otherwise partially
burnt fuel passes into the flues, where it may re-ignite and cause serious
damage. In one case which recently came under our notice the
"secondary" flame did damage in a boiler side flue, and in another
instance it occurred in an economiser flue.
Owing to the long flames, and also to the possibility of this re-ignition of
the waste gases after partial burning, the shell plates may be exposed to high
gas temperature and, therefore, when burning oil, the scaling of shell plates
is as important as that of furnace plates.
In using oil in horizontal cylindrical furnaces with the grates removed, the
lower parts become effective heating surface. These parts are commonly
neglected as regards scale, but require the same attention as other parts and
should be kept quite clean at the water-side when exposed to heat.
The oil flame should not strike the furnace plates directly, as, apart from any
risk of overheating, the flame is thereby cooled and combustion checked,
resulting in black smoke and waste of fuel.
Seams should be protected from the direct impact of flame.
It is not necessary to line the furnaces with brickwork if the plates are clean
at the water-side, but a screen or bridge of brickwork for the flames to play
upon is a great aid to combustion. If the furnaces are lined the flames do not
part with their heat at these parts, and the furnace tubes or combustion
chamber beyond the brickwork lining have to take up excess heat. In vertical
boilers the flame should be inclined downwards on to brickwork, care being
taken to protect the base seam. Water-tube boilers with large combustion spaces
lend themselves well to oil firing, but here also care should be taken to keep
the flame from striking directly on the water tubes, drums and headers.
Flue gas explosions are more apt to occur with oil fuel than with coal or coke,
and precautions are necessary in order to avoid them.
Unburnt or partially burnt oil in the flues is liable to explode.
Volumes of unburnt gas may pass into the flues if, for instance, a burner fails
temporarily and is not at once shut off or relighted. Again, undue restriction
of air supply to the burners will result in filling the flues with partially
burnt gas. Both these conditions are dangerous, and we recommend that the
following precautions be observed in order to avoid gas explosions :—
The flames at the burners should be under constant observation. Should a flame
be accidentally extinguished it should at once be relighted, or the oil shut
off. If the burner has been discharging unburnt oil for an appreciable time the
oil must at once be shut off and time allowed for the flues to clear before
relighting.
The dampers should never be closed when burning oil. Steam output should be
regulated only by the oil, steam, and air supply at the burners.
Under proper conditions there should be a light grey smoke from the chimney ;
dense black smoke indicates incomplete combustion, and white smoke shows that
excessive air is being used.
Using oil and coal or coke together is not altogether desirable, although very
convenient when the available coal supply is inadequate. In ordinary furnaces,
such as in the Lancashire boiler, the combustion space above the grate is too
small for the satisfactory combustion of oil fuel, and it is more satisfactory
to burn coal only in one furnace and oil only in the other.
Oil leakages are, of course, very objectionable, and may be dangerous
especially if the oil finds its way into boiler flues. It will vaporise there
and very likely explode.
 |
 |
|