11th September 1926, Page: 59, Column: 1
The Gulliford Firedamp Detector
The development of a firedamp detector for application to miners' electric hand
lamps is described in Fuel in Science and Practice by C. S. W. Grice
and A. G. Gulliford. The introduction of a reliable form of
firedamp detector, as an integral part of an electric hand lamp, should give to
the miner using such a lamp the same feeling of confidence as is experienced by
the user of a flame lamp, who knows that he has at hand ready means of firedamp
detection and is not entirely dependent upon the observations of others.
The two chief properties by reason of which methane differs from the normal
constituents of the mine atmosphere are : (1) Its combustibility; and (2) its
low density. Detectors that attempt to make use of the latter property may be
neglected for the purpose of this paper, but it may be remarked, in passing,
that their design is complicated by the necessity to obviate the effects of
changes of temperature and of humidity of the air.
The fact that methane is combustible can be utilised in a number of ways to
determine the quantity of it present in air. For example, the quantity can be
estimated: (1) By a visible methane "cap" over a glowing platinum
spiral. (2) By the contraction in volume resulting on its explosion in a closed
vessel. (3) By the contraction in volume on burning it in a closed vessel by
means of a glowing metal spiral. (4) By the rise in temperature of a catalytic
body heated in the mixture, as indicated by : (i) Its expansion in volume, (ii)
Its increase in electrical resistance, (iii) Its change in appearance.
The Gulliford firedamp detector is an apparatus designed to indicate if there
is more than a given percentage of firedamp in a mine atmosphere. It is not
designed to measure different percentages of firedamp contained in different
atmospheres, but merely to act as means of warning the miner that he is working
in an atmosphere that may become dangerous.
The apparatus is what may be termed the "heated wire" type, but the
fundamental difference in its design, as compared with previous apparatus of
the same type, lies in the fact that it does not require, nor does it rely
upon, the use of a measuring instrument or of a calibrated scale. It consists
of a measured length of platinum fuse-wire of small diameter, which can be
switched, at will, into the bulb circuit of a miners' electric lamp. So soon as
the electric current passes through the fuse-wire it becomes heated, and its
dimensions are so proportioned with respect to the source of current supply as
to ensure that it will glow a dull red when in pure air. If firedamp is present
in the air it burns on the surface of the wire, the temperature of which
increases in consequence. Ultimately, if sufficient firedamp is present, the
wire fuses. A platinum wire used in this way is not affected by the
"ageing" that has been found to militate against its use where the
estimation of firedamp is dependent on the measurement of, for example, small
changes in the electrical resistance of the wire.
In the Gulliford detector the platinum fuse-wire is of such a length (3 mm.),
and of such a diameter (0.035 mm.) that it will fuse if, when an electric
current at 2.0 volts is passing through it, it is exposed to an atmosphere
containing 3 per cent. or more of methane, and will not fuse, but will glow
more brightly, if exposed to an atmosphere containing less than 3 per cent. of
methane. The correct dimensions were arrived at mainly by the method of trial
and error.
When the wire fuses, the lamp bulb is extinguished, but the light can be
recovered by operating a switch.
Laboratory tests have been made with the detector fitted to two types of 2-volt
electric hand lamps, namely, the "Ceag" and the "Oldham."
In addition to these tests, experiments were made to determine the length of
fuse-wire suitable for use with the new type "Edison" cap lamp. The
new type "Edison" cap lamp has an alkaline accumulator at 2.6 volts
and a bulb of higher current consumption than that of most 2-volt lamps.
Successful results were obtained with a fuse-wire 6 mm. in length. It should
similarly be possible to fit the detector to any of the many varieties of
miners' electric lamps ; but, in order to do so, it would be necessary to
standardise the length of fuse with reference to the current consumption of the
bulb of the lamp and the voltage of the accumulator. Similarly, with any
particular make of lamp, care should be taken that there is no marked variation
in the current consumption of the bulb when replacement becomes necessary.
A number of different lamps have been fitted with the detector and used for
tests in colliery workings in which firedamp was present.
The method of test was to take the lamp fitted with the detector into various
parts of the colliery and to estimate the amount of firedamp present by the
observation of the "cap" on the lowered flame of a safety-lamp.
Samples of the atmosphere were also taken and subsequently analysed. So soon as
the percentage of firedamp present had been estimated by means of the
flame-lamp the detector was used, and in every instance, when the atmosphere
contained 3 per cent. or more of firedamp, the fuse was blown and the bulb was
extinguished ; whilst on no occasion when the atmosphere in the mine contained
less than 3 per cent. did extinction occur.
Before the detector was taken into a colliery it was tested at the Mines
Department Testing Station at Eskmeals and approved as safe. Apart from the
fact that it has passed the statutory tests, it can be stated, as a result of
experiments carried out for the Safety in Mines Research Board by Mr. W. C. F. Shepherd
on the ignition of gases by hot wires, that the heating and
fusion of a platinum wire of such fine diameter as that used for the fuses is
incapable of igniting any mixture of methane and air.
The results of experiments show that the Gulliford detector is a satisfactory
device provided that the standard length of fuse-wire is maintained. Whilst not
fulfilling all the functions of an official's gas-testing lamp, in that it only
indicates when 3 per cent. or more of methane is present in the mine air and
cannot be used as means of estimating the actual amount, it will indicate to
the user of an electric hand lamp when the atmosphere in which he is working is
likely to become dangerous. The detector is easy to manipulate and simple of
construction, and it does not impair the safety of an electric hand lamp.
 |
 |
|