12th February 1913
Mining Electrical Engineers
Cables For Shafts
The question of cables for shaft of mines was brought up by Mr. E. Kilburn Scott, at a meeting of the Association of Mining Electrical Engineers.
The author pointed out that cables for shafts of mines differed from those in other situations because the question of weight was so important a factor. In order to reduce the weight the cables should be worked at high tension and insulated accordingly.
Although aluminium had not been used for shaft cables there was every reason to suppose that the lighter metal would be found distinctly advantageous. Contrary to the general supposition, it was much stronger from the point of view of supporting its own
weight than was copper.
All metal work which was continuous from the top to the bottom of a shaft should be utilized as the earth return. There was nothing in the Revised Rules against this being done, or indeed requiring shaft cables to be armoured. In any event the cross
section of the armour of a high tension cable was likely to be too small to earth properly the low tension underground feeders. Even where it was not convenient to use existing metal work it would be much cheaper to suspend wire ropes in the shaft for
the earth return than to place the same amount of metal round a cable as armour.
The marked success which had followed the use of silicious tire rubber as a mechanical protection on cables subjected to moisture and hard wear and tear pointed to its being also a very suitable material for cables permanently installed in shafts.
Further, as sinking cables must necessarily be insulated with rubber, the addition of tire rubber in place of specially flexible armouring seemed a reasonable proposal. By placing the winch in insets as the shaft descended the length of sinking cable
could be limited to that at which cable without armour was feasible.
Hitherto casing had always been made of sawn planks, the joints of which were difficult to keep tight. The use of telegraph poles sawn longitudinally and having the joints between the halves closed by steel hoops was suggested. Casing made in that way
should be cheap and easy to erect, and it would form a complete protection to the enclosed cable. As regards preservatives for casing and cleats saccharine impregnated into the wood had no action on insulations or metals ; also when impregnated along
with arsenic it was a solution of the white ant difficulty which was so troublesome in mining work overseas.
 |
 |
|
Names mentioned in this article
|
 |
 |
| Name | Age | Occupation | Notes |
| Scott, E. Kilburn | | | |