An assistant machineman received a fatal electric shock from the frame of a 2½ h.p. electrically driven heading machine at Choppington "B" Colliery, Northumberland. An electrician installed the machine on the previous day, and in attaching a new plug to the outbye end of the flexible cable, had connected the earthing conductor of the cable to a live terminal and one of the power conductors to the earthing terminal of the plug. The error would have been discovered if the apparatus had been tested before being put into service, as required by General Regulation 131 (c) (ii).
|
|||||||||||||||||||||||||||||
![]() |
||||||||
|