An electrician, aged 20, was killed at Broomhill Colliery, Northumberland. He had dismantled a twin break switch for a 5 h.p. motor driving a semi-portable pump on a 500 Volt A.C. circuit, insulated system, and had refixed it in its new position. On restarting the motor it ran satisfactorily, but he took the lid off the spreading box at the supply end of the switch and shortly afterwards fell to the ground dead. Artificial respiration was attempted for two hours but without success. The insulation of the two tails in the spreading box was found to be split, exposing the bare wires, Probably deceased realised that he had damaged the insulation in passing the cores through the switch casing, and determined to inspect them again after starting up the motor. A very slight bum on the end of his right fore-finger suggests that he made contact with a live bare core in the spreading box and received a fatal shock. He was standing in water at the time and was found by post-mortem examination to be prone to shock owing to status lymphaticus. This was the first occasion deceased had done work without supervision. He was not an authorised person and was probably weary after a long shift.
|
|||||||||||||||||||||||||||||
![]() |
||||||||
|