One fatal accident under this heading occurred at West Auckland Colliery, Durham, resulting in the death of a pumpman. He had been having some food in an old refuge hole used for changing wet clothing, and lighted by an electric carbon filament lamp. On rising from his seat he touched the lamp holder and received an electric shock due to a connection between an exposed part of one of the live conductors and the fitting. The lighting cable was a rubber insulated 12 core telephone cable, the individual conductors being single No. 20 S.W.G. wires. The 110 volt lighting circuit was fed from an intermediate tapping on the phases of the 440 volt winding of a 3-phase transformer. Contributory causes of the accident were (a) the metal work of the lamp fitting was not earthed; (b) there was defective contact between the terminal of the cable used for connecting the neutral point of the 3-phase winding of the transformer to the transformer casing and so to earth; (c) The existence of a breakdown of the insulation on one phase of a switch connected to the 440 volt terminals of the transformer. As a result it was possible for the pressure between earth and one- of the lighting circuit conductors to rise to approximately 350 volts on the occurrence of a fault on the conductor connected to the 440 volt terminals of the transformer.
|
|||||||||||||||||||||||||||||
![]() |
||||||||
|