Electricity. At Risehow Colliery, Cumberland, a trailer was lifting a full tub on to the rails with the assistance of another trailer, and while doing so he put his hand upon a flexible cable supplying alternating current at 500 volts to a small motor driving an auxiliary fan. The cable was moist and there was a transverse cut in the sheath which penetrated to one of the live phases, and he received a fatal shock. There was a gate end switch near, but the other lad knew nothing about it and he ran for assistance. A deputy was 200 yards away, and when he arrived he shut off the current and tried artificial respiration without success. Armoured cable should have been in use in such a position, and the accident would not then have occurred.
|
|||||||||||||||||||||||||||||||||
![]() |
||||||||
|