| Notes: | Deceased came by a terrible death. A Lancashire boiler (one of a battery of nine) had to be damped down for the week-end. The boiler was isolated from the steam range, and the feed water was shut off. Presently it was noticed that the water level in the boiler was too high, and it was decided to run some off, through the blow-off valve. This valve was under the floor plates in front of the boilers, and the water from it ran first into the ash road, and then into a culvert. A stoker removed the plates, and standing on a tram of ashes, tried to open the valve by means of a key. He did not succeed, and was advised to leave it alone until the boiler had cooled down. However, he got another key and standing in front of the valve outlet, opened it. The hot water scalded him to death. The arrangement was bad. The pipe should have led into a special culvert. It should be said that the valve could have been operated from the ordinary floor level of the boilers. The stoker was an experienced man, and it can only be supposed he was obsessed with the one idea of getting the valve opened |