West Wylam CollieryMiscellaneous Notes and IncidentsWest Wylam Colliery, Northumberland, on 2nd July (Below Ground — Naked light mine) Gate-end switches and a small hauler had been moved about 25 yards inbye following the advance of the working face. About 8 a.m: the following morning a message was received on the surface that the small hauler could not be started, and an electrician, with an apprentice, was sent inbye to see what was wrong. The gate-end switch controlling the hauler was of the light-weight pattern and had been designed some years ago as a room switch for the American method of mining. The switch was designed so that the integral isolator was mechanically interlocked with the front access cover. This made it necessary to switch off the isolator before the front cover could be opened to give access to the switch interior. Apparently the electrician suspected some defect within the switch and did not cut off the power at the section switch some 85 yards outbye. He opened the switch cover to examine the interior, and it is presumed that he used his screwdriver to close the isolator, as a humming noise was heard during this examination. Apparently dirty contacts on the 'START' push button on the front access cover were suspected, and the apprentice was instructed to clean them. This work had apparently been completed, and, when the electrician was attempting to close the front access cover by inserting his hand into the switch interior to move the small flexible cables connected to the earth leakage relay to prevent them being trapped by the cover, he received fatal injuries. The deputy, who was present, after asking where the switch was, and the electrician replying that it was outbye, immediately ran out to the district switch, and cut off the power. He returned quickly to apply artificial respiration, which was continued for 1¼ hours until the arrival of a doctor, but there was no response. The electrical system was three-phase, 50 cycles, 600 volts, with the neutral point earthed. The roadway in which the accident occurred was wet, and the electrician was perspiring freely, his clothing being wet. The doctor's examination shewed burns on the left hand, and left buttock. When the apparatus was examined after the accident no defect of the mechanical interlock could be found, although the isolator was in the 'ON' position with the front access cover open. It was later demonstrated that, by inserting the point of a screwdriver into the slot of the isolator spindle and levering against the surrounding shroud, it was relatively easy to close the isolator when the front access cover was open. As the electrician had been using a screwdriver at the time it is presumed that the apparatus was made live in this manner and that his hand came into contact with the terminals on the earth leakage relay. Earth leakage protection was fitted in the switch outbye but this did not operate. Source: Report of H.M. Principal Electrical Inspector of Mines for 1949, from a copy held in the Scottish Mining Museum, Newtongrange, Midlothian
|
![]() |
||||||||
|
Mail: Webmaster |
Back |
Home |
Copyright © 1999-2024 by The Durham Mining Museum and its contributors Registered Charity No: 1110608 Page last updated: 31 Dec 2022
|
Search |
|
|||