Usworth CollieryMiscellaneous Notes and IncidentsUsworth Colliery, Durham (Above ground — Explosion of switch) An electrician and a compressor attendant had transported a draw-out type 2,750 volts switch from the colliery workshops where it had been overhauled, to its pedestal in the surface compressor room where it was to be used to control the 300 H.P. compressor motor. The electrician had been instructed to fill the tank with oil before it was put to work and to do so proposed to lift the switch and insert its guide rods into the guide tubes on the pedestal part of the apparatus. The switch tank could then be removed for the oil filling. The switch guide rods were inserted into the guide tubes, but when the switch was moved forward to make sure it was free to move, it travelled too far, and its contacts touched those in the pedestal. An explosion occurred within the switch, shattering the tank and burning both men. As the interlocks were in order it is presumed that, to enable the switch to be pushed forward, the electrician had to manipulate the switch handle past the interlock stop. Since fusion was found on the pedestal live contacts and on the switch contacts, it is possible that the switch had been inadvertently closed as it was reaching the end of its travel. There was evidence of a severe flashover having occurred between phases and the earthed metal within the switch tank and, as there was no leakage protection on the system, the switch on the main switch-board tripped out on overload, interrupting the supply to the 150 horse power fan. With most types of modern pedestal draw-out oil- immersed circuit-breakers, a blanking plate is provided to prevent access to the live busbar contacts when the switch is drawn forward. In this position, the blanking plate can be raised or lowered without difficulty and when raised, ensures safety to the electrician who has to work on the switch. On the design of switch concerned, however, it is not possible, when the switch is drawn forward, to raise or lower the blanking plate because of lack of space between the switch and pedestal. According to the evidence, the switch was lifted on to its pedestal while the busbar contacts were exposed, and the plate was in the lowered position. Production of this type of switch had ceased over 20 years ago, and as the manufacturers can suggest no modification which can be applied to overcome this defect, great care must be observed with this design of switchgear to ensure safety to the electrician working upon the apparatus. It is generally necessary to switch off elsewhere, before any work is commenced. Source: Report of H.M. Principal Electrical Inspector of Mines for 1949, from a copy held in the Scottish Mining Museum, Newtongrange, Midlothian
|
![]() |
||||||||
|
Mail: Webmaster |
Back |
Home |
Copyright © 1999-2024 by The Durham Mining Museum and its contributors Registered Charity No: 1110608 Page last updated: 31 Dec 2022
|
Search |
|
|||