Although not reportable under the Coal Mines Act, 1911, I should like to call attention to an accident presenting very unusual and disquieting features, in which three ponies were electrocuted at Hamsterley Colliery, Durham. The electrical system was 3-phase, 550 volts, with the neutral point earthed. During the flitting of a coal cutter the insulation broke down between one phase and earth in the plug connector at a gate-end switch, and, owing to the armouring of the 3-phase cable not being connected to the surface earth plate, the defect was, in fact, a short circuit between one phase and earth. The leakage current, having no direct metallic path to earth, was flowing through such casual earths as there were upon the circuit. It would pass through the ground and through any metallic conductors such as haulage ropes, rails and signalling wires in contact with earth. Owing to some peculiarities in the strata, aided by the disposition of the haulage rails, sufficient current was flowing in the haulage road, at a point 100 yards from the place where the insulation failed, to set up such a voltage gradient between the ground and the rails as to give a fatal electric shock to three ponies coming inbye. If the regulations respecting proper earthing and routine examinations and tests had been observed this accident would not have occurred.
Source: 1928 Mines Inspectors Report