Fishburn CollieryMiscellaneous Notes and IncidentsFishburn Colliery, Durham (Above ground): An Electricity Board engineer received an electric shock and burns as a result of contact with live conductors during the work of cleaning the insulators of a cable trifurcating box attached to a reactor in the surface substation. The power supply was 2,750 volts, 3-phase, 50 cycles, A.C., and the neutral point of the system was earthed. The surface substation comprised a bank of five 2,750 volt switches, two of which were used for incoming supplies from the Electricity Board, two were shaft feeder switches, and the fifth was not in use. Shaft feeder switch No. 1 with its associated reactor was the property of and was maintained by the Electricity Board, the National Coal Board being responsible for the other shaft feeder switch (No. 3), and reactor. Another shaft feeder (No. 2) was also supplied from the standby alternator in the colliery power station some 500 yards distance from the surface substation. The three shaft feeders were in No. 1 shaft and were connected to separate switches on the Harvey Level pit bottom switchboard. Shaft feeder No. 1, however, was also connected to a switchboard in the High Harvey Level inset in the shaft to provide a supply for apparatus in this level. (See diagram over). On the day of the accident, the Electricity Board engineer proposed to examine the busbars and switches in the substation as bitumen was leaking from part of their switchgear. Arrangements for cutting off the power supply from the Electricity Board had been made with the electrician-in-charge at the colliery to enable this work to be carried out. As power was necessary for the pumps underground, the standby alternator in the power station was started and an electrician sent to the Harvey Level to arrange the switches so that the colliery alternator could supply the pumps there and also the pumps in the High Harvey Level. The engineer from the Electricity Board had, in the meantime, cut off the incoming supply and opened the shaft feeder switches, and also discharged and earthed the busbars of the bank of switches in the surface substation. One of the 2,750 volt switches in the power station with an overload setting of 120 amperes and another in the Harvey Level with a setting of 110 amperes tripped and so drew attention to the development of a fault. The engineer working in the surface substation was found on a ladder with his legs locked in the rungs. He was immediately removed from the ladder and laid on the floor. Fortunately, a competent first-aid man was available and artificial respiration was at once commenced. Within about six minutes he had recovered. When a doctor arrived, he gave the injured man an injection and had him removed to hospital. An examination of the apparatus showed that the injured man had been cleaning the insulators of the reactor in the run of shaft feeder No. 1. As this reactor was the property of the Electricity Board, either he or one of his colleagues would normally do this work. The injured man, however, did not appear to be aware that shaft feeder No. 1 and the reactor, being supplied from the standby alternator in the power house, would be live through shaft feeder No. 2 and the interconnecting switches at the Harvey and High Harvey levels. The electrician-in-charge said, in evidence, that he did not know that the engineer intended to enter the reactor cubicle or he would have given a warning against this. Divided responsibility for ownership and maintenance of electrical apparatus in the same substation is always liable to result in misunderstandings, especially, as in this case, when one shaft feeder switch and reactor was owned by the National Coal Board and another by the Electricity Board. The management was asked to arrange to take over responsibility for all feeder switches and reactors. Source: Report of H.M. Principal Electrical Inspector of Mines for 1951, from a copy held in the Scottish Mining Museum, Newtongrange, Midlothian
|
![]() |
||||||||
|
Mail: Webmaster |
Back |
Home |
Copyright © 1999-2024 by The Durham Mining Museum and its contributors Registered Charity No: 1110608 Page last updated: 31 Dec 2022
|
Search |
|
|||