On December 17th, a heavy discharge of lightning took place at East Hetton Colliery, Co. Durham, at the time that the men were descending the pit. Some of the men in the cage felt a slight shock and one man jumped out of the cage. No one was injured. Various men and boys working near the shaft and on the main engineplanes up to a distance of 1,800 yards from the shaft felt shocks, and in some cases saw sparking from the haulage and rapper ropes.
Various parts of the electric system both above and below ground at East Hetton were affected, as also were some portions of the surface plant at Trimdon Grange Colliery belonging to the same owners.
An overhead line of bare conductors connects the stations of the two collieries. The line was protected at both ends by lightning arrestors of the horn type set with a gap of 5/32.
At East Hetton Colliery two chimneys were struck, a 10-inch water pipe 7 feet in the ground was cracked, motors were tripped, ammeters damaged or burnt out, and all the underground switches were tripped.
At Trimdon Grange Colliery the switches at both ends of the overhead line were tripped, and two switches on motors on the surface were tripped.
From an investigation of all the circumstances it seems clear that the earth plates at the two collieries were defective; they were small in themselves and not placed in well-chosen situations.
Source: 1917 Mines Inspectors Report