Underground fires. — Six of the dangerous occurrences reported to me were underground fires. Three of these occurred at Clara Vale Colliery, Durham.
In one instance some stonemen and rolleywaymen observed a glow in the haulage road and intake airway near a small aircooled two-stage electrically-driven air compressor used to supply power for pneumatic picks. The machine was stopped and a small quantity of oil found to be burning on top of a valve casing. Subsequent investigation showed that there had been burning on some sections of the radiator intercooler and it seemed probable that the fire originated in an explosion or ignition of vaporized oil in the intercooler. The occurrence was, in itself, trifling but seemed to be of considerable importance as indicating a potential danger which might, in other circumstances, have more serious consequences. For the benefit of other users of similar machines I offer some observations on the installation and care of the machines.
The compressor-house should, of course, be constructed solely of non-inflammable materials and care should be taken to keep it free from accumulations of oil or other inflammable material It should be so arranged that a cooling air current passes through, and so that the air supply to the machine inlet filter, in particular, is as cool and clean as possible. The number and severity of bends in the supply mains should be reduced to a minimum.
The recommendations of the manufacturers regarding the type of oil to be used, the frequency of oil changing and the intervals between the examination and cleaning of valves and intercooler sections should be observed. In some cases these recommendations may be based on the assumption that the machine will be worked only during one shift daily and it seems obvious that when machines are being worked almost continuously (as they sometimes are) the recommended intervals should be correspondingly reduced.
It would appear that, in the case of some machines, heat is not dissipated so quickly or so effectively as in the case of similar machines working in comparable conditions. In any case of difficulty the manufacturers would, doubtless, be glad to advise.
Special attention should be paid to the provision of fire fighting aids in such situations.
In a second instance a fire occurred at the top of the upcast shaft, which was not used for raising mineral at all and not normally for lowering or raising men. The banksman at the downcast shaft, some 100 feet distant, saw smoke at the top of the upcast. He at once raised the alarm, communicating with the under-manager who was nearby at the time. The ventilating fan was stopped and the fire quickly attacked with water. The Elswick rescue brigade arrived within a quarter of an hour and the fire was extinguished within less than an hour of its discovery.
The wood shaft covering, some buntons between the surface level and the fan drift, and wood doors provided as part of the means for reversing the air current were partially burned. The winding ropes were burned through and the small cages fell to the shaft bottom. The cause of the fire remained unexplained. The occurrence stresses the potential danger involved in the use of inflammable material in such a situation.
In a third instance a small fire was due to carelessness on the part of a stoneman, who left a pipe in his coat pocket without taking proper precautions to ensure that there was no tobacco left burning in it. Naked lights were used on the outbye side of caution boards and workmen were allowed to smoke.
Source: 1938 Mines Inspectors Report